Data Centre Liquid Cooling (Liquid & Liquid series)CDU

PRODUCT DETAIL

Deployment &Connection

Liquid &Liquid CDU
·Rack Integration: Designed for direct installation within server racks to achieve compact, close-proximity cooling.
·Localized Heat Dissipation: Efficiently manages coolant distribution and heat exchange for single or a few cabinets, targeting local hotspots.
·Flexible Expansion: Modular design allows flexible deployment and scaling to meet demand, suitable for high thermaldensity areas.
Manifold
·Balances flow to prevent local overheating and supports hot-swapping to reduce maintenance costs.
·Adapts to liquid cooling needs of multiple power architectures, helping optimize cabinet PUE and improving heat dissipation reliabilit.

Liquid-Cooled Rear Door
·Active Heat Dissipation: Equipped with fans or pumps, forcing airflow through the heat exchanger to more efficienthremove server heat.
·High-Density Eficiency: Handles ultra-high-density cabinets, delivering exceptional cooling performance while maintain.ing stable data center temperature.
·Precise Control: Adiusts fan or pump speed based on load for finer cooling management and energy savings.
Water Pump
·Works with water manifolds to regulate flow, ensuring uniform heat dissipation forend equipment.

Water Tank
·Absorbs flow fluctuations caused by simultaneous water demand from multiple cabinets, ensuring stable coolant supplyto each cabinet.
Dry Cooler
·Requires no water consumption, suitable for water-scarce areas, and avoids watelconsumption and scale issues assocated with traditional coolina towers.
·Stabilizes the temperature of the primary-side coolant, supplving low-temperatureliquid for subsequent cycles to ensure system heat dissipation efficiency.

Refrigeration Module
·Eneray Saving & Consumption Reduction: The liguid cooling system reduces significant power consumption required foair cooling, delivering higher cooling efficiency compared to traditional cooling methods.
·High -Density Deployment: As high-density Al applications expand, traditional air cooling solutions fail to meet heat dissipation demands, High-efficiency chillers support efficient heat exchange.
Product Parameter
| Parameter Category | Parameter Item | Specifications |
| I. Core Performance | Rated Cooling Capacity | 50kW |
| Heat Exchange Temp Difference | 4℃ @50kW cooling | |
| Max Operating Power | ≤700W | |
| II. Fluid Circuit | Secondary Water Supply |
100LPM, 1Bar |
| Secondary Coolant | Ethylene glycol / PG25 | |
| Pump Redundancy | 1+1, auto seamless switch | |
| Primary Pressure Drop | 0.8Bar (80LPM, 20% glycol) | |
| Secondary Temp Control | 10~45℃, dew point control | |
| III. Piping & Filtration | Primary Pipe Interface | 1-1/2" sanitary clamp |
| Primary Volume | 6L | |
| Secondary Pipe Interface | 1-1/2" sanitary clamp, optional quick connect | |
| Secondary Filter | 50μm cleanable filter | |
| Secondary Volume | 10L | |
| IV. Electrical | Input Power | Single-phase AC 85~265V, 50/60Hz |
| Power Redundancy | Dual power redundancy | |
| V. Physical & Env | Dimensions & Weight | 175×445×900mm, 65kg |
| Operating Noise | <58dBA @3m | |
| VI. Monitoring System | Flow Monitoring | Primary & secondary full flow |
| Pressure Monitoring | Supply/return/filter/system differential | |
| Temperature Monitoring | Primary inlet, secondary supply/return | |
| Env Monitoring | Room temp & humidity real-time | |
| Communication | RS485 Modbus, TCP/IP SNMP, DCIM compatible | |
| VII. Auxiliary Components | Water Make-up & Vent | Auto pump make-up + manual vent |
| Expansion Tank | 1L for pressure stabilization | |
The above data is for reference only; specific data is subject to the product nameplate. |
||